Surveyor Portable DFR DDR
- Transient Fault Recording and Analysis
- Long Term Disturbance Recording
- Continuous Waveform Recording
- Continuous Phasor Recording
- Power Quality Monitoring
- E-MAX Display/Analysis Software included
- Sampled Data Streaming Compliant
- IEEE - C37.118-2005
- IEC 61850
- NERC Compliant
- NERC - PRC-002-2
- IEEE C37.232
Related Products
Accessories
Surveyor
The E-MAX Portable DFR/DDR monitors voltages, currents and digital (event) inputs in an electrical power system environment to detect and record out-of-limit conditions. When such a condition is sensed, data including a specified prefault period is captured and stored in the recording system. The Recorder transmits the data automatically or on command to one or more locations.
The Recorder has non-volatile solid-state drive storage for data retention.
All functions are controllable at the Recorder site as well as remotely from any site with compatible equipment and software. The Recorder has security functions to restrict remote access to authorized users.
Accessories include a Portable Touchscreen Monitor, a lightweight travel case, with or without wheels and an optional accessory kit to convert the E-MAX Portable quickly and easily to a standard 19” rack mount unit.
Analog Inputs | 8 to 16 Inputs |
Analog Input Range | Voltage: 0 to 500 Vac rms or Current: 0 to 200 Amp |
Accuracy | Better than 0.1% of full scale |
Analog Isolation | 2500 Volts rms |
Maximum Sampling Rate | 15,360 samples/channel/second (256 samples/cycle) |
Standard Base Sample Rate | 5760 samples/channel/second |
Digital/Event Inputs | 16 to 32 Inputs |
1. Input Configuration | N.O. or N.C. (Software Selected) |
2. Input Voltage | 125 Vdc Nominal standard —24, 48, 250 Vdc available |
3. Isolation | 2500 VDC (To Ground) and between inputs |
4. Resolution | 1/Analog Sample Rate |
Sensors | |
1. Analog Sensors | Over-, Under- limits and rate software sensors on each channel Symmetrical component, harmonic, frequency swing sensors |
2. Operation Limiters | Individual Channel: Software Settable up to 15 minutes per fault |
3. Event Sensors | Individual Programmable (N.O., N.C., Trigger on ALARM and/or RETURN) |
4. External Sensors | Contact or voltage input |
Continuous Recording | Complies with NERC PRC-002-2 and IEEE C37.232. Default: Records up to 10 Days. |
Long term Recording | Phasor recording - simultaneous with Transient recording |
Sample rate is software selectable: 1 sample/cycle, 1/2 sample/cycle, 1/4 sample/cycle, 1/8 sample/cycle |
|
Programmable Record Length - 90 days maximum length |
|
Logs of signals, power and frequency | |
High Speed Transient Recording | |
Prefault Period | Up to 99 cycles. Default setting: 10 cycles |
Postfault Period | Up to 999 cycles. Default setting: 12 cycles |
Record Storage | Nonvolatile data storage on local SATA drive |
Resolution | 16 bit |
Power Supply | DC/DC Converter: 90 - 320 Vdc / 120 Vac. 28-48 Vdc and 250 Vdc Available Current Limited / Overvoltage protected |
Controller | Intel Quad Core 64 bit CPU. 8 Gb RAM standard |
1 USB 3.0 Port, 5 USB 2.0 Ports, Gb Ethernet Port |
|
Graphic Output | Supports color inkjet, laser or dot matrix printers |
Graphics display on optional monitor | |
Data Storage | 500 Gb or larger SATA Solid State Drive |
Clock Options | GPS Timing - IRIG B Decoder Internal (1 kHz or TTL), External GPS Clock |
Accuracy | Better than 20 µs |
Communications Capability | |
1. To Master Stations | Transfer of data files through Windows FTP Service |
Functions with multiple-Master system | |
Windows Remote Desktop for Remote Control | |
2. Email | Automatic reporting to multiple user selected email addresses |
3. LAN and WAN | Software supports communication via TCP/IP |
Software Supplied | |
1. Master Station & Recorder | Microsoft Windows 10® |
Complete remote control, test and data retrieval, display and screen manipulation |
|
Remote setting of program and system parameters |
|
Remote setting of program and system parameters |
|
2. Display/Analysis Software | E-MAX WinGrafDisp (Waveform Data) |
E-MAX Phasorview (Phasor Data) | |
Environmental Characteristics | |
Operating Temperature | 0 To 60 degrees C |
Storage | -20 to 65 degrees C |
Relative Humidity | 0 to 95% R.H. non-condensing |
Surge Withstand Capability | ANSI C37.90.1 1989 |
Quality Certification | ISO 9001:2015 |
International Standards Compliance | |
Safety | IEC 60255-2 IEC 60255-4 IEC 60255-5 |
Immunity | IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 IEC 61000-4-6 |