RAW-2, RAW-2D
* denotes UL Recognized model
Part Number | Model | Nominal | Minimum | Nominal Resistance |
632A311* | RAW-2 | 125 V | 90 V | 15 K |
632A312* | RAW-2 | 48 V | 30 V | 6.5 K |
632A313* | RAW-2 | 250 V | 175 V | 35 K |
632A314* | RAW-2 | 24 V | 15 V | 1.5 K |
632A315* | RAW-2D | 125 V | 90 V | 15 K |
632A316* | RAW-2D | 48 V | 30 V | 6.5 K |
632A317* | RAW-2D | 250 V | 175 V | 35 K |
632A318* | RAW-2D | 24 V | 15 V | 1.5 K |
632A322 | RAW-2D | 120 Vac | 11 K | |
632A323 | RAW-2D | 230 Vac | 20 K |
RAW-2, RAW-2D
- Continuous monitoring of trip coil continuity
- Self-monitoring - long-life
- Can also be used as a self-latching, high speed target for trip indication
- UL Recognized
- Simple Installation
The RAW-2 is a panel mounted relay for monitoring trip coil continuity. The relay itself is self-monitoring since opening of any of the series components causes the same conditions as the loss of the trip coil. On breaker opening, the RAW-2 is energized through the breaker “B” contact.
Output contacts for the RAW-2 Relay are 2 form C. The RAW-2 is available for 125 Vdc, 48 Vdc, 24 Vdc and 250 Vdc input. The RAW-2D contains the additional feature of delay on drop-out. The delay of approximately 200 milliseconds is designed to allow auxiliary contacts to transfer without alarm. The relay cases are molded of rugged glass-coupled acetal copolymer having high dielectric strength and top located terminals for ease in mounting and connection.
- Isolation 1500 Vdc minimum contact or coil to Coil or coil to ground.
- Contact Rating Switching - 50 Watts 1.5 A max.; 500 V max.
Carrying - 3.2 A max. - Operating Temperature -25 to 650 C
- Storage Temperature -54 to 850 C
- Altitude 0 - 50,000 feet
- Life Expectancy 1 x 105 Operations
- Vibration Insensitive to Vibration below 1 Khz
- Noise Immunity ANSI C37.90a-1974
- Cycling Rate 60 cps Maximum