RAW-2, RAW-2D

* denotes UL Recognized model

Part Number Model Nominal Minimum Nominal Resistance
632A311* RAW-2 125 V 90 V 15 K
632A312* RAW-2 48 V 30 V 6.5 K
632A313* RAW-2 250 V 175 V 35 K
632A314* RAW-2 24 V 15 V 1.5 K
632A315* RAW-2D 125 V 90 V 15 K
632A316* RAW-2D 48 V 30 V 6.5 K
632A317* RAW-2D 250 V 175 V 35 K
632A318* RAW-2D 24 V 15 V 1.5 K
632A322 RAW-2D 120 Vac 11 K
632A323 RAW-2D 230 Vac 20 K
Related Products
Accessories

RAW-2, RAW-2D

  • Continuous monitoring of trip coil continuity
  • Self-monitoring - long-life
  • Can also be used as a self-latching, high speed target for trip indication
  • UL Recognized
  • Simple Installation

The RAW-2 is a panel mounted relay for monitoring trip coil continuity. The relay itself is self-monitoring since opening of any of the series components causes the same conditions as the loss of the trip coil. On breaker opening, the RAW-2 is energized through the breaker “B” contact.

Output contacts for the RAW-2 Relay are 2 form C. The RAW-2 is available for 125 Vdc, 48 Vdc, 24 Vdc and 250 Vdc input. The RAW-2D contains the additional feature of delay on drop-out. The delay of approximately 200 milliseconds is designed to allow auxiliary contacts to transfer without alarm. The relay cases are molded of rugged glass-coupled acetal copolymer having high dielectric strength and top located terminals for ease in mounting and connection.